Hp Integrity BL870c Server-Blade Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Počítačový hardware Hp Integrity BL870c Server-Blade. HP Integrity BL870c Server-Blade User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - HP Seismic Rack User Guide

HP Seismic Rack User GuideHP Part Number: AH343-9000BPublished: April 2012Edition: 3

Strany 2

2 Site Preparation GuidelinesThis chapter includes these topics:• “System Cabling” (page 10)• “DC Power System Warnings” (page 11)• “Cooling and Humid

Strany 3 - Contents

DC Power System WarningsWARNING! To reduce the risk of electric shock or damage to the equipment, HP BladeSystemDC power supplies must be installed in

Strany 4 - 4 Contents

Cooling Airflow DirectionEach enclosure includes its own forced-air cooling fans or blowers. Air flow for each enclosureenters from the front of the r

Strany 5 - About This Document

the lighting fixtures and electrical outlets affects servicing operations, consider an equipment layoutthat takes advantage of existing lighting and e

Strany 6

Electrostatic DischargePreventing electrostatic dischargeTo prevent damaging the system, be aware of the precautions you must follow to set up the sys

Strany 7 - HP contact information

3 SpecificationsEnvironmental SpecificationsValueSpecificationTemperature range1-5 to 50 ºC ambient temperatureOperating-40 to 70 ºCNon operatingRelat

Strany 8 - Documentation feedback

Unpacking area: When moving the cabinet off the shipping pallet, you need approximately 9 feet(2.74 meters) on one side of the cabinet to allow you to

Strany 9 - 1 System Overview

4 Installation Preparation StepsNOTE: Preparation for the installation of any equipment in a Telco facility is dictated by theTelcordia Technologies G

Strany 10 - 2 Site Preparation Guidelines

PurposeTool9/16-inch socket wrench with 1/2-inch drive ratchet• Install caster supports on racks• Remove screws that secure racks to their shipping pa

Strany 11 - Cooling and Humidity Control

5 Installing the Seismic RackThis chapter includes these topics:• “Drilling Floor Anchoring Holes” (page 19)• “Unpacking and Moving the Seismic Rack”

Strany 12 - Operational Space

© Copyright 2008, 2012 Hewlett-Packard Development Company, L.P.Legal NoticeConfidential computer software. Valid license from HP required for possess

Strany 13 - Zinc Particulates

• Ear plugs or other ear protection• Rubber bulb (ear syringe available from any pharmacy)• Try square• Standard screw driver• #2 Phillips screwdriver

Strany 14 - Electrostatic Discharge

3. Load the drill bit:a. Unlock the chuck on the rotary hammer drill.b. Insert the concrete drill bit in the chuck.c. Lock the chuck.4. Set the depth

Strany 15 - 3 Specifications

6. Unload the seismic rack from the pallet, see:“Moving the Seismic Rack off the Pallet” (page 26).7. Bolt the seismic rack to the floor, see:“Bolting

Strany 16 - 16 Specifications

1. Open the doora. Insert the key in the lock and turn it one quarter turn counterclockwise.b. Remove the key. You will not be able to open the latch

Strany 17 - Gathering Necessary Tools

Removing the Side PanelsIf your rack has side panels, also remove them before installing mounting brackets and otherhardware.1. For the seismic rack:

Strany 18 - Preparing the Work Space

1. For the seismic rack: Turn the quarter-turn fasteners securing the kickplate. Pull the kickplateaway from the base of the rack.For the seismic rack

Strany 19 - 5 Installing the Seismic Rack

• For the seismic rack: Using a 9/16-inch socket and 1/2-inch ratchet, unscrew the eight screws(four on each side of the rack) securing the rack to th

Strany 20

NOTE: For sites that are not equipped with overhead hoists, installing casters onto the racks isrequired to move the racks off the pallets or around t

Strany 21

10. Using the 3/4-inch wrench, raise the rack on the casters by turning the caster jack screwsclockwise, a little at a time, until the rack is high en

Strany 22 - Removing the Rack Door

Unpacking and Moving the Seismic Rack 29

Strany 23

ContentsAbout This Document...5This Manual Supplements Other Manuals

Strany 24 - Removing the Kickplate

6. Install caster wheel and thread block into caster arm using two hexhead bolts.WARNING! When moving the cabinet with the casters installed, the cabi

Strany 25

1. Ensure the eight leveling feet are as high as they will go. They should be shipped from thefactory in the fully raised position. If necessary, adju

Strany 26 - Installing the Casters

4. For the seismic rack only: Install the blank drip trays provided in the hardware kit over unusedanchor holes in the base of the rack using the prov

Strany 27

Bolting the Seismic Rack to a Raised FloorWARNING! An unsecured rack is prone to tipping. This rack is designed to be bolted to a floor.Because the ra

Strany 28

Figure 2 Anchor Rod Assembly For Raised Floor7Raised floor1Socket head bolt cap2Spring washer8Saddle nut9Raised floor channel3Flat washer4Nylon bushin

Strany 29

To join two cabinets together, you need two brackets, 12 round washers, and four 5/8-inch bolts.Cabinets are joined at the top at two anchor positions

Strany 30 - Positioning the Seismic Rack

Figure 4 Joining a Seismic Rack R2 to Other Seismic Racks Top ViewFigure 5 Joining Adjacent CabinetsConnecting Site GroundCAUTION: Site power (rails A

Strany 31 - Removing the Casters

• Before making any crimp connections, coat the bare wire and base connectors withanti-oxidant.• Use star washers between the lug and the rack ground

Strany 32

3. Using an 11-mm socket driver, torque the nuts to 40 in-lbs (4.5 N-m).Figure 7 Site Ground Cable Connection to Bottom of Seismic Rack R2Intracabinet

Strany 33

Enclosures in the rack must each have their own ground connections to the rack grounding rail.For specific ground connections for an enclosure, see th

Strany 34

Disconnecting the Seismic Rack From the Pallet...25Moving the Seismic Rack off the

Strany 35

6 Regulatory Compliance NoticesIn This Section:• “Regulatory Compliance Identification Numbers” (page 40)• “Federal Communications Commission Notice”

Strany 36 - Connecting Site Ground

Class A EquipmentThis equipment has been tested and found to comply with the limits for a Class A digital device,pursuant to Part 15 of the FCC Rules.

Strany 37 - Connecting Site Ground 37

Mouse Compliance StatementThis device complies with Part 15 of the FCC Rules. Operation is subject to the following twoconditions: (1) this device may

Strany 38

Japanese NoticeBSMI NoticeKorean NoticeClass A EquipmentClass B EquipmentLaser ComplianceThis product may be provided with an optical storage device (

Strany 39

Product in accordance with US FDA regulations and the IEC 60825-1. The product does not emithazardous laser radiation.Each laser product complies with

Strany 40 - FCC Rating Label

Power Cord Statement for JapanPower Cord Statement for Japan 45

Strany 41 - Modifications

A Site Power CablesSite cables and lugs must be provided by the customer or the installation provider for the customer.HP does not provide these items

Strany 42 - European Union

IndexAAir conditioning, 11Anchor holes,marking concrete floor, 20drilling into concrete floor, 20tools required, 19CCommunications interference, 13Coo

Strany 43 - Laser Compliance

About This DocumentThis manual describes the tasks for site preparation, installation, and servicing the HP SeismicRack. This manual supplements docum

Strany 44 - Battery Replacement Notice

The user must press the Return key after typing the input.[ ] Brackets Brackets enclose optional syntax items. For example:TERM [\system-name.]$termin

Strany 45

$process-name.#su-nameLine Spacing If the syntax of a command is too long to fit on a single line, eachcontinuation line is indented three spaces and

Strany 46 - A Site Power Cables

Documentation feedbackHP welcomes your feedback. To make comments and suggestions about product documentation,send a message to [email protected]

Strany 47

1 System OverviewSeismic RackThe seismic rack is 36U and has a 1200 lb payload limit. For detailed specifications for the seismicrack, see “Seismic Ra

Komentáře k této Příručce