HP power and cooling technologies for the
data center
Technology brief, 2
nd
edition
Introduction ......................................................................................................................................... 2
ProLiant server efficiency....................................................................................................................... 2
High-efficiency features ..................................................................................................................... 2
Power monitoring and reporting tools ................................................................................................. 3
Power control tools ........................................................................................................................... 3
Power distribution ................................................................................................................................ 4
HP Intelligent Power Discovery ........................................................................................................... 4
HP Power Advisor ............................................................................................................................ 6
HP uninterruptible power supplies ...................................................................................................... 6
Cooling .............................................................................................................................................. 7
HP 10000 G2 Rack Air Duct ............................................................................................................. 8
HP Modular Cooling System G2 ........................................................................................................ 8
Data center power management with HP Insight Control .......................................................................... 9
Data center power topology management ........................................................................................... 9
Data gathering and archiving .......................................................................................................... 10
Power monitoring ........................................................................................................................... 11
Data center thermal profiles ............................................................................................................. 12
Available power reporting .............................................................................................................. 14
HP Performance Optimized Datacenters ............................................................................................... 15
HP POD 40c and 20c .................................................................................................................... 16
HP POD 240a ............................................................................................................................... 17
Conclusion ........................................................................................................................................ 18
For more information .......................................................................................................................... 19
Zobrazit stránku 0
1 2 3 4 5 6 ... 18 19

Shrnutí obsahu

Strany 1 - edition

HP power and cooling technologies for the data center Technology brief, 2nd edition Introduction ...

Strany 2 - ProLiant server efficiency

10 Insight Control can discover and communicate with iPDUs to retrieve the power topology (see ―Discover the power distribution topology‖ above) and

Strany 3 - Power control tools

11 Figure 6: Power consumption graph in Insight Control showing the and average and peak observed power consumption and the power cap for a rack of

Strany 4 - Power distribution

12 generalized practices. The difference between the Calibrated Max Power and Peak Observed Power represents the potential power capacity that you c

Strany 5

13 Before Insight Control can generate the temperature profile, you need to describe the physical positions of your systems and racks. You can do th

Strany 6 - HP Power Advisor

14 At the rack level, the Power/Layout tab displays a specific rack configuration with power distribution devices, enclosures, and servers. The view

Strany 7 - Cooling

15 new devices. Insight Control also polls the iPDUs daily and updates the rack configuration if a server is moved or a new server is plugged into a

Strany 8 - HP Modular Cooling System G2

16 HP POD 40c and 20c The POD 40c is 40 feet (12 m) long with 1100U of rack capacity and twenty-two 50U 19-inch (482 mm) deep racks (Figure 12). It

Strany 9

17 As a result, the HP POD 40c and 20c can have a PUE ratio as low as 1.25 depending on the configuration of the IT equipment and the water-cooling

Strany 10

18 We can ship the HP POD 240a in as little as 12 weeks. For more information on the EcoPOD, visit http://h17007.www1.hp.com/us/en/whatsnew/june/060

Strany 11 - Power monitoring

© Copyright 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Strany 12 - Data center thermal profiles

2 Introduction In this technology brief, we describe a broad range of HP products and technologies that raise energy efficiency, maximize use of the

Strany 13

3 consuming less energy. The ability to use Common Slot Power Supplies across multiple platforms simplifies maintenance and reduces inventory. All H

Strany 14 - Available power reporting

4 HP Dynamic Power Capping We use HP Dynamic Power Capping technology in most of the enterprise-class G5 ProLiant servers and beyond. Dynamic Power

Strany 15

5 Discover the power distribution topology Our IPD solution works with ProLiant servers with iLO 2 (firmware v2.0 or newer) or iLO 3 (firmware v1.0

Strany 16 - HP POD 40c and 20c

6 management GUI and Insight Control include a Power Cycle Control switch that lets you cycle power simultaneously to the redundant outlets for each

Strany 17 - HP POD 240a

7 Figure 2: Conventional AC power distribution using an online double conversion UPS Newer data centers may have more efficient power distributi

Strany 18 - Conclusion

8 racks below about 10 kW. Today’s high-density IT racks can generate significantly more heat, creating hot spots that need supplemental cooling or

Strany 19 - For more information

9 circulated (Figure 4). For more information, see the HP Modular Cooling System G2 Rack Overview at http://h10010.www1.hp.com/wwpc/us/en/sm/WF05a/3