Moving and stabilizing a rack
WARNING!
The physical siz
e and weight of the rack requires a minimum of two people to move. If one person tries
to mo ve the rack , injury may occur.
To ensure stability of the rack, always push on the lower half of the rack. Be especially careful when
moving the rack over any bump (e.g., door sills, ramp edges, carpet edges, or elevator openings). When
the rack is moved over a bump, there is a potential for it to tip ov er.
Moving the rack requires a clear, uncarpeted pathway that is at least 80 cm (31.5 in) wide for the
60.3 cm (23.7 in) wide, 42U rack. A vertical clearance of 203.2 cm (80 in) should ensure suf cient
clearance for the 200 cm (78.7 in) high, 42U rack.
CAUTION:
Ensurethatnoverticalorhorizontalrestrictionsexistthatwouldpreventrackmovementwithout
damaging the rack.
Make sure that all four leveler feet are in the fully raised position. This process will ensure that the casters
support the rack weight and the feet do no impede movement.
Each rack requires an area 600 mm (23.62 in) wide and 1000 mm (39.37 in) deep (see Figure 28).
CXO8238
A
1
3
2
4
5
6
7
8
2
Figure 28 Single rack conguration oor space requirements
1. Front door 2. Rear door
3. Rack width 600 mm 4. Service area width 813 mm
5. Rear service area depth 300 mm 6. Rack depth 1000 mm
7. Front service area depth 406 mm 8. Total rack d epth 1706 mm
Ifthefeetarenotfullyraised,completethefollowingprocedure:
1. Raiseonefootbyturningthelevelerfoothexnutcounterclockwiseuntiltheweightoftherackis
fully on the caster (see Figure 29).
2. Repeat Step 1 for the other feet.
82
Enterprise Virtual Array hardware components