HP UPS Management Module User Guide Part Number 435656-002 September 2007 (Second Edition)

Strany 2 - Audience assumptions

Overview 10 Configuration A This figure illustrates a UPS with a management module installed that is serially attached to a server running the UPS Po

Strany 3 - Contents

Regulatory compliance notices 100 Regulatory compliance notices Regulatory compliance identification numbers For the purpose of regulatory complianc

Strany 4 - Contents 4

Regulatory compliance notices 101 energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio

Strany 5 - Contents 5

Regulatory compliance notices 102 Cet appareil numérique de la classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Can

Strany 6 - Contents 6

Regulatory compliance notices 103 Japanese notice BSMI notice

Strany 7 - Overview

Alert messages 104 Alert messages UPS alarms This management module enables you to send an email notification or SNMP trap to specified recipients i

Strany 8

Alert messages 105 Alarm text Description Input Out of Range • Input (Utility) fault: Measured input voltage has exceeded the upper voltage limit

Strany 9

Alert messages 106 Alarm text Description Manual Load Dumped The load power is off. This alarm is used to record the date and time of an EPO event

Strany 10 - Configuration B

Systems Insight Manager integration 107 Systems Insight Manager integration Systems Insight Manager overview Use HP Systems Insight Manager to: • D

Strany 11 - Configuration C

Systems Insight Manager integration 108 Discovering the management module HP SIM automatically detects management modules as part of the device disc

Strany 12 - Configuration D

Systems Insight Manager integration 109 To register the MIB: 1. Copy the MIB to the HP\Systems Insight Manager\mibs folder. 2. From the HP\System

Strany 13 - Configuration E

Overview 11 Item Description 1 Server with UPS Power Protection Agent installed 2 Network 3 UPS with management module installed Conf

Strany 14 - Configuration F

Security considerations 110 Security considerations Security considerations overview The management module implements strict security for two import

Strany 15 - Web interface requirements

Optional power monitoring using SNMP 111 Optional power monitoring using SNMP SNMP monitoring Battery status, power status, events, and traps can be

Strany 16 - Software Browser

Updating the firmware 112 Updating the firmware Updating the firmware overview To update the management module firmware from an application, downloa

Strany 17 - Component identification

Redundant configuration 113 Redundant configuration Configuring the software for redundancy 1. Install the UPS Power Protection Agent on a machine

Strany 18 - Required tools

Redundant configuration 114 g. Click Save Changes to return to the Attached Devices screen. h. Repeat steps e through g to configure the agent inf

Strany 19

Mass configuration 115 Mass configuration Using the HP UPS Management Upgrade Utility Use the HP UPS Management Upgrade Utility to configure multipl

Strany 20 - Connecting the network cable

Acronyms and abbreviations 116 Acronyms and abbreviations ASCII American Standard Code for Information Interchange DMA direct memory access DRAM d

Strany 21

Acronyms and abbreviations 117 MII media independent interface NTP network time protocol POST Power-On Self Test RAM random access memory SIM Sy

Strany 22

Index 118 A About menu 76 accessing software, browser 41 accessing software, system tray icon 42 adding an attached device 69 adding new user

Strany 23 - Connecting devices

Index 119 firmware, updating 112 firmware, version 49, 76 front panel components 17 G GUI installation, agent 27 H hardware installation 18

Strany 24

Overview 12 Configuration D This figure illustrates a redundant configuration with serial connections. Item Description 1 UPS A 2 Server 3 Netwo

Strany 25

Index 120 redundant configuration 12, 13, 14, 15, 94, 113 regulatory compliance identification numbers 100 regulatory compliance notices 100, 1

Strany 26 - Installation overview

Overview 13 Configuration E This figure illustrates a redundant configuration with network connections. Item Description 1 UPS A 2 UPS B 3 Serve

Strany 27

Overview 14 Configuration F This figure illustrates a redundant configuration with serial and network connections. Item Description 1 UPS A 2 Se

Strany 28

Overview 15 Configuration G This figure illustrates a redundant configuration with dual subnet. Item Description 1 Subnet A 2 UPS A 3 Server 4 S

Strany 29

Overview 16 Software Browser Monitor resolution Minimum supported resolution of 1024 x 768, 16-bit high color (maximize browser window for optimal d

Strany 30

Component identification 17 Component identification Front panel Item Description 1 Serial device connectors 2 Environmental connector (for f

Strany 31

Installing the HP UPS Management Module 18 Installing the HP UPS Management Module Required tools No. 2 Phillips screwdriver Installing the managem

Strany 32 -

Installing the HP UPS Management Module 19 3. Install the management module along the alignment channels in the option slot. 4. If the UPS is pow

Strany 33

© Copyright 2007 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Strany 34

Installing the HP UPS Management Module 20 Checking the Error LED If the Error LED illuminates red or flashes red, see the "Troubleshooting (on

Strany 35

Installing the HP UPS Management Module 21 Connecting the configuration cable 1. Connect a DB-9 to RJ-45 adapter to a serial connector on the host

Strany 36

Installing the HP UPS Management Module 22 1. On the host computer, click Start, and select Programs>Accessories>Communications>HyperTermi

Strany 37 - Script method

Installing the HP UPS Management Module 23 Use the HP UPS Management Module Service Menu to configure the minimum settings required to access the ma

Strany 38

Installing the HP UPS Management Module 24 2. Connect one end of a network cable to the RJ-45 connector on the adapter. 3. Connect the other end

Strany 39

Installing the HP UPS Management Module 25 5. Press the Reset button on the management module front panel.

Strany 40

Installing the HP UPS Power Protection Agent 26 Installing the HP UPS Power Protection Agent Installation overview Install the UPS Power Protection

Strany 41 - Accessing the web interface

Installing the HP UPS Power Protection Agent 27 NOTE: You might need to reboot after installing the agent on Windows®. Installing the agent us

Strany 42 - System tray icon

Installing the HP UPS Power Protection Agent 28 5. Read the license agreement, select I accept the terms in the license agreement, and then click N

Strany 43 - Browser security alert

Installing the HP UPS Power Protection Agent 29 7. Click Next to install the agent in the default folder that is displayed. To specify a different

Strany 44

Contents 3 Contents Overview...

Strany 45 - Navigating the web interface

Installing the HP UPS Power Protection Agent 30 9. Click Finish to complete the install wizard and continue with the configuration process. NO

Strany 46 - Home tab

Installing the HP UPS Power Protection Agent 31 12. Click Finish to close the configurator. The service starts automatically. Wait until the syste

Strany 47

Installing the HP UPS Power Protection Agent 32 • Change any items that should be unique, such as the Management Server IP address, through the nor

Strany 48 - Alarms menu

Installing the HP UPS Power Protection Agent 33 • Select Configure HP UPS Management Module from the HP UPS Management Module option in the Start P

Strany 49 - Identification menu

Installing the HP UPS Power Protection Agent 34 The installer launches a separate configuration program. The script displays: Please enter a server

Strany 50

Installing the HP UPS Power Protection Agent 35 • Change any items that should be unique, such as the Management Server IP address, through the nor

Strany 51 - Parameters menu

Installing the HP UPS Power Protection Agent 36 o Edit the /etc/sysconfig/boot file and change RUN_PARALLEL="yes" to RUN_PARALLEL="no

Strany 52

Installing the HP UPS Power Protection Agent 37 Installing the agent locally or remotely using the Installation Script method 1. The agent can be i

Strany 53 - Manual Control menu

Installing the HP UPS Power Protection Agent 38 The script displays: Please enter a server to allow connections from. 11. Enter the IP address of

Strany 54 - Logs tab

Installing the HP UPS Power Protection Agent 39 3. From the directory that contains all five files, run ./SetupRA -s -f DevManRA.ini to install sile

Strany 55

Contents 4 Uninstalling components from HP-UX systems ...

Strany 56 - Application Log menu

Installing the HP UPS Power Protection Agent 40 NOTE: Some files might remain following the uninstallation and can be removed manually.

Strany 57 - Setup tab

HP UPS Management Module web interface 41 HP UPS Management Module web interface HP UPS Management Module web interface overview The web interface g

Strany 58 - User Accounts menu

HP UPS Management Module web interface 42 NOTE: For a complete list of the browser requirements, see "Web interface requirements (on page 15

Strany 59 - Network menu

HP UPS Management Module web interface 43 For instructions on changing the password, see "My Account menu (on page 57)." Admin session lo

Strany 60 - Network Management menu

HP UPS Management Module web interface 44 • The certificate is untrusted, meaning it was signed by a certifying authority that is unknown to your b

Strany 61 - System Information tab

HP UPS Management Module web interface 45 3. Perform any other steps necessary to verify the identity of the management module. 4. After verifying

Strany 62 - SNMP Managers tab

HP UPS Management Module web interface 46 o The legend displays the meaning of symbols used in the interface. Expand and collapse the legend by cli

Strany 63 - Remote Access tab

HP UPS Management Module web interface 47 The following example is for a single module UPS. The following example is for a parallel UPS. Battery,

Strany 64 - Event Notifications menu

HP UPS Management Module web interface 48 Input, Output, and Load is displayed graphically on the left side of the screen. The color on each meter r

Strany 65 - Events tab

HP UPS Management Module web interface 49 The following example is for a parallel UPS. Click the UPS tabs to view detailed information for each of

Strany 66 - Email Setup tab

Contents 5 Agent does not install on RH Itanium...

Strany 67 - Attached Devices menu

HP UPS Management Module web interface 50 The following example is for a single module UPS. The following example is for a parallel UPS.

Strany 68 - • Red—Critical

HP UPS Management Module web interface 51 Click the UPS tabs to view detailed information for each of the sub units in the parallel system. The para

Strany 69 - Controlling a load segment

HP UPS Management Module web interface 52 The following example is for a single module UPS. The following example is for a parallel UPS.

Strany 70

HP UPS Management Module web interface 53 Click the UPS tabs to view detailed information for each of the sub units in the parallel system. The para

Strany 71 - Power Fail menu

HP UPS Management Module web interface 54 To reset the management module: 1. Select Restart Management Module. 2. Click Execute Command. NOTE:

Strany 72 - Advanced power fail settings

HP UPS Management Module web interface 55 The following example is for a parallel UPS. The following information is displayed for each event: • Se

Strany 73 - Shutdown Events menu

HP UPS Management Module web interface 56 Application Log menu Click Application Log in the left navigation frame to display the Application Log scr

Strany 74 - Scheduled Shutdowns menu

HP UPS Management Module web interface 57 Setup tab Menu options listed under the Setup tab include: • My Account menu (on page 57) • User Account

Strany 75 - Help tab

HP UPS Management Module web interface 58 User Accounts menu Click User Accounts in the left navigation frame to access the User Accounts screen. Th

Strany 76 - About menu

HP UPS Management Module web interface 59 2. Click Delete Users to delete the user account. The account is removed and no longer appears on the Use

Strany 77 - Info & Updates menu

Contents 6 HP contact information...

Strany 78 - Accessing the Service Menu

HP UPS Management Module web interface 60 c. Select the time zone from the dropdown box. d. Enter the number of hours that should pass between eac

Strany 79 - Navigating the menus

HP UPS Management Module web interface 61 System Information tab This screen enables administrators to enter contact information for the management

Strany 80 - Service Menu

HP UPS Management Module web interface 62 Trap Receivers tab This screen enables administrators to enter information for servers that should receive

Strany 81 - Power Protection submenu

HP UPS Management Module web interface 63 To configure SNMP managers: 1. Enable the SNMP manager configuration for up to five servers. 2. Enter th

Strany 82 - SNMP submenu

HP UPS Management Module web interface 64 o Upload the SSL certificate: i. Open the SSL certificate file with a text editor. ii. Select all conte

Strany 83 - Emails submenu

HP UPS Management Module web interface 65 Events tab This screen enables administrators to define the event notifications, emails, or SNMP traps the

Strany 84 - System Configuration submenu

HP UPS Management Module web interface 66 Email Setup tab This screen enables administrators to configure email event notifications. To configure t

Strany 85 - User Accounts submenu

HP UPS Management Module web interface 67 SNMP Traps tab This screen enables administrators to configure SNMP trap event notifications. To configur

Strany 86

HP UPS Management Module web interface 68 The overall status of the UPS and each load segment is indicated by a colored block in the top left cor

Strany 87 - Troubleshooting

HP UPS Management Module web interface 69 For more information about the possible redundant configuration status icon combinations, see "Redund

Strany 88 - Battery Test did not run

Overview 7 Overview Introduction The HP UPS Management Module enables you to monitor, manage, and control power environments of up to five devices th

Strany 89 - Certificate error

HP UPS Management Module web interface 70 2. Enter the device name or description in the Description field. 3. Select the type of device in the Ty

Strany 90

HP UPS Management Module web interface 71 NOTE: The management module shuts down the operating system gracefully. Use the SDScript file for other

Strany 91 - Input frequency shows zero

HP UPS Management Module web interface 72 minutes after power fails that the management module should wait before starting to shut down the load seg

Strany 92 - Troubleshooting 92

HP UPS Management Module web interface 73 Low Battery—Selected Low Battery—Deselected Shutdown Settings Conserve Battery Power The management modu

Strany 93 - Troubleshooting 93

HP UPS Management Module web interface 74 1. Select Shutdown? for the event you want to configure. 2. Enter the number of minutes to wait between

Strany 94 - Redundant UPS status

HP UPS Management Module web interface 75 Add/Edit Scheduled Shutdowns screen 1. In the Frequency field, select one of the following: o One Time—S

Strany 95

HP UPS Management Module web interface 76 • About menu (on page 76) • Contents menu (on page 77) • Info & Updates menu (on page 77) About me

Strany 96 - Troubleshooting 96

HP UPS Management Module web interface 77 Contents menu Click Contents in the left navigation frame to display the Contents screen. This screen prov

Strany 97 - Troubleshooting 97

HP UPS Management Module Service Menu 78 HP UPS Management Module Service Menu HP UPS Management Module Service Menu overview The HP UPS Management

Strany 98 - Troubleshooting 98

HP UPS Management Module Service Menu 79 Terminal emulation session Use a terminal emulation program to access the HP UPS Management Module Service

Strany 99 - Technical support

Overview 8 HP UPS Power Protection Agent overview The HP UPS Power Protection Agent runs on a local or network server and allows the management modul

Strany 100 - Class B equipment

HP UPS Management Module Service Menu 80 • Press the Enter key to refresh the screen. • The management module resets automatically to allow config

Strany 101 - Modifications

HP UPS Management Module Service Menu 81 Battery submenu Option number Submenu Description 1 Battery Installed Date Enables you to enter the

Strany 102 - • EMC Directive 2004/108/EC

HP UPS Management Module Service Menu 82 Network Settings submenu Option number Submenu Description 1 Static IP Address Enables you to set t

Strany 103 - BSMI notice

HP UPS Management Module Service Menu 83 Option number Submenu Description 2 Read Community String Enables you to enter or change the Read commu

Strany 104 - Alert messages

HP UPS Management Module Service Menu 84 Email Recipient submenu Option number Submenu Description 1 Receiver Email Enables you to enter or

Strany 105

HP UPS Management Module Service Menu 85 Network Time Protocol submenu Option number Submenu Description 1 Primary NTP Server Enables you to

Strany 106

HP UPS Management Module Service Menu 86 Option number Submenu Description 3 Administrator Privilege Enables you to designate a user as an adminis

Strany 107

Troubleshooting 87 Troubleshooting ASCII character sequence Esc+Shift+9 directs all serial communication to the iLO port for the HP ProLiant DL380 G4

Strany 108

Troubleshooting 88 Battery Test did not run Possible Cause: The UPS is On Battery. Action: The UPS must be in a certain state before the battery test

Strany 109

Troubleshooting 89 Certificate error Possible Cause: Internet Explorer 7 does not recognize the SSL certificate. Action: • Install an SSL certific

Strany 110 - Security considerations

Overview 9 Hardware and software Suggested minimum requirements SUSE Linux Enterprise Server 9 for AMD64 and Intel® EM64T with Service Pack 3 SUSE

Strany 111 - SNMP monitoring

Troubleshooting 90 Test LED flash error code Description 1 Permanently on DRAM failure 2 2 flashes DMA Mem to Mem error 3 3 flashes IRQ erro

Strany 112 - Updating the firmware

Troubleshooting 91 HPFlash does not install image.bin on a Pentium III Symptom: The image.bin file is not installed on a Pentium III during a serial

Strany 113 - Redundant configuration

Troubleshooting 92 Invalid IP address Action: Verify that the IP address entered is valid. Links in traps and emails do not work correctly for Linux

Strany 114 - Redundant configuration 114

Troubleshooting 93 4. Verify that the network settings are correct. No power Action: Verify that the UPS is connected to a working outlet and that

Strany 115 - Mass configuration

Troubleshooting 94 Receiving a security error Symptom: Security error: Domain Name mismatch message when trying to browse with SSL. Possible Cause: T

Strany 116 - Acronyms and abbreviations

Troubleshooting 95 Events Agent status Management Server 1 status Management Server 2 status Two UPSs are on battery power and redundant power is los

Strany 117

Troubleshooting 96 • Verify the command line parameters are correct. • Verify the configuration .ini file is valid. • Verify the Setup.iss destina

Strany 118 - Index 118

Troubleshooting 97 • For Linux, the file can be found at /usr/local/DevMan. • For HP-UX, the file can be found at /opt/DevMan. Unable to obtain a

Strany 119 - Index 119

Troubleshooting 98 Unexpected problems occur with the web interface and Service menu Possible Cause: The management module was removed from one UPS a

Strany 120 - Index 120

Technical support 99 Technical support Before you contact HP Be sure to have the following information available before you call HP: • Technical su