Raised floor cutouts for MCS 5042
A complete MCS 5042 installation typically requires the following floor cutouts in a raised-floor
facility:
Standard rack configuration:
• One floor cutout for the chilled water hoses, drain hoses of the cooling unit
• One floor cutout for the power cords and data cables of the computer equipment rack (including
power supply to the MCS 5042). For details on the top openings, see the section Cable openings.
Raised floor panels vary in size globally, but all create virtual grid lines or seams where panels come
together. These seams are ideal for positioning computer racks on the raised floor. Figures 26 through
30 reference the locations of rack attributes aligned with raised floor seams to provide critical
dimensions for floor cutouts.