Hp Tower Uninterruptible Power System Uživatelský manuál Strana 1

Procházejte online nebo si stáhněte Uživatelský manuál pro Počítačové příslušenství Hp Tower Uninterruptible Power System. HP Tower Uninterruptible Power System User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 80
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
HP R/T3000 G2 UPS
User Guide
Abstract
This document includes installation, configuration, and operation information for the HP R/T3000 G2 UPS. This document is for the person who
installs and maintains power products. HP assumes you are qualified in the servicing of high-
voltage equipment and trained in recognizing hazards
in products with hazardous energy levels.
Part Number: 651176-002
June 2012
Edition: 2
Zobrazit stránku 0
1 2 3 4 5 6 ... 79 80

Shrnutí obsahu

Strany 1 - User Guide

HP R/T3000 G2 UPS User Guide Abstract This document includes installation, configuration, and operation information for the HP R/T3000 G2 UPS. This

Strany 2

Component identification 10 Item Description 4 Load segment circuit breaker 5 Load segment 1 (two NEMA 5-20R T-Slot receptacles) 6 Load segment cir

Strany 3 - Contents

Component identification 11 R/T3000 INT rear panel Item Description 1 UPS option card 2 USB communications port 3 Serial communications port 4

Strany 4 - Contents 4

Component identification 12 IMPORTANT: Pressing and holding the On button without utility present normally initiates a battery start and the UPS a

Strany 5 - Contents 5

Installation 13 Installation Precautions Save these instructions. This document contains important safety instructions that should be followed durin

Strany 6 - Contents 6

Installation 14 • Hex nuts • Cage nuts • Cage nut-fitting tool Selecting a site WARNING: To prevent fire or electric shock, install the unit

Strany 7 - Component identification

Installation 15 WARNING: To reduce the risk of personal injury or damage to the equipment, be sure that: • The leveling feet are extended to the

Strany 8 - UPS front panel controls

Installation 16 3. Install cage nuts or clip nuts into the rear of the rack. 4. Insert screws through the mounting rail into the cage nuts or clip

Strany 9 - HP UPS R/T3000 models

Installation 17 5. Tighten the wing nuts or hex nuts. 6. Install the rear stabilization bracket using wing nuts. Wait until the unit is installed

Strany 10 - Item Description

Installation 18 2. Install the mounting ears on the chassis using the screws provided. 3. With one person on each side, lift the chassis to rail l

Strany 11 - REPO port

Installation 19

Strany 12 - ERM rear panel

© Copyright 2011, 2012 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warr

Strany 13 - Installation

Installation 20 Attaching the UPS front bezel Connecting the host computer CAUTION: Only one communications port can be connected to the host

Strany 14 - Readying the equipment

Installation 21 Connecting the serial communications port CAUTION: Use only the computer interface cable supplied with the UPS to connect the co

Strany 15 - Installation 15

Installation 22 WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a UPS installed in a computer equipment

Strany 16 - Installation 16

Installation 23 • Avoid allowing the wires to hang in the rear of the UPS. • Use tie wraps and tie wrap blocks to secure the wires tightly to the

Strany 17 - Installing the UPS in a rack

Installation 24 The ground bonding cable is not included. Connecting the UPS to utility power WARNING: To prevent injury from electric shock

Strany 18 - Connecting the battery leads

Installation 25 CAUTION: Do not plug laser printers into the UPS output receptacles. The instantaneous current drawn by this type of printer can o

Strany 19 - Installation 19

Installation 26 IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to devices. The batteries charge to: • 80 per

Strany 20 - Connecting the host computer

Installation 27 4. Attach the chassis to the rack using the supplied screws. Connecting the battery leads

Strany 21 - Connecting the REPO port

Installation 28 Attaching the ERM front bezel

Strany 22 - Installation 22

Installation 29 Connecting the ERM to the UPS 1. Remove the screws, and then remove the ERM connector bracket from the UPS. 2. Connect the ERM ca

Strany 23 - Installation 23

Contents 3 Contents Component identification ...

Strany 24 - Installation 24

Installation 30 3. Attach the ERM connector bracket to the UPS as a cord retention bracket for the ERM cable. 4. To install a second ERM: a. Remo

Strany 25 - Charging the UPS batteries

Installation 31 Installing the optional UPS Network Module NOTE: It is not necessary to power down the UPS before installing the UPS Network Mo

Strany 26 - Installing the ERM in a rack

Installation 32 4. If the UPS is powered up, you can be sure that the UPS Network Module is seated properly and communicating with the UPS by verify

Strany 27

Installation 33 Connecting the battery leads WARNING: To prevent personal injury from electric shock or damage to the equipment, remove the batt

Strany 28 - Installation 28

Installation 34 Attaching the UPS front bezel Attaching the tower conversion stands WARNING: To reduce the risk of personal injury or damage t

Strany 29 - Installation 29

Installation 35 Installing the ERM as a tower Before installing the unit, review and adhere to all warnings provided in "Precautions (on page 1

Strany 30 - Charging the ERM batteries

Installation 36 WARNING: To reduce the risk of personal injury or damage to the equipment, the tower conversion stands must be properly attached w

Strany 31 - Installation 31

Installation 37 o For the rear bracket, use the screws removed from the chassis. Continuing the ERM installation To continue the ERM installation,

Strany 32 - Installation 32

Installation 38 Installing the extension bars (if included)

Strany 33 - Rotating the logo badge

Installation 39 Connecting and securing the power cords

Strany 34 - Continuing the installation

Contents 4 Attaching the tower conversion stands ... 35 C

Strany 35

UPS operations 40 UPS operations Modes of operation The UPS has five modes of operation: • Standby mode (on page 40) • Operate mode (on page 40) •

Strany 36

UPS operations 41 For the location of buttons, see "UPS front panel controls (on page 8)." For the location of LEDs, see "UPS front p

Strany 37 - Installation 37

UPS operations 42 NOTE: If the On and Off buttons are simultaneously pressed, the Off button has priority over the On button. Button Asser

Strany 38 - Installation 38

UPS operations 43 Available settings Parameter Associated LED Explanation (when LED is illuminated) 110/220 Nom Battery Fault Nominal output

Strany 39 - Installation 39

UPS operations 44 Silencing an audible alarm To silence an alarm, press the Test/Alarm Reset button ("UPS front panel controls" on page 8)

Strany 40 - UPS operations

Maintenance 45 Maintenance Removing the UPS front bezel Removing the ERM front bezel Replacing the batteries To replace the batteries:

Strany 41 - Auto-Bypass mode

Maintenance 46 1. Read and observe the requirements in "Important battery safety information (on page 46)" and "Battery care and stor

Strany 42 - Configuring the UPS

Maintenance 47 When a battery alarm sounds, initiate a UPS battery self-test to verify that battery replacement is required. If the Battery Fault LE

Strany 43 - Initiating a self-test

Maintenance 48 IMPORTANT: Do not pull the battery leads when removing or installing the batteries. To replace the components, reverse the remov

Strany 44 - Powering down the UPS

Maintenance 49 Replacing the UPS To remove the UPS: 1. Power down all attached load devices. 2. Power down the UPS ("Powering down the UPS&qu

Strany 45 - Maintenance

Contents 5 Low battery shutdowns ...

Strany 46

Maintenance 50 3. Remove the two screws securing the option card and slide the card out. To replace the component, reverse the removal procedure.

Strany 47 - Obtaining new batteries

Maintenance 51 5. In the tree displayed in the left panel, click the Ports (COM & LPT) branch to expand. 6. Double-click the port that is assig

Strany 48 - Maintenance 48

Maintenance 52 The Advanced Settings screen appears. 5. Select an available USB port number from the COM Port Number drop down menu. 6. Click OK

Strany 49 - Replacing the ERM

Power management 53 Power management Power Protector software HP Power Protector software ensures maximum power reliability of computer systems thro

Strany 50 - Updating the UPS firmware

Power management 54 • Delays reboot by load segment after a power outage to sequence the startup of system components.

Strany 51

Troubleshooting 55 Troubleshooting LED troubleshooting Utility LED On Battery LED On Bypass LED Self Test LED Battery Fault LED Site Wirin

Strany 52

Troubleshooting 56 Off On Off On—Battery capacity <25% On—Battery capacity >25% On—Battery capacity >50% On—Battery capacity >75% Off UP

Strany 53 - Power management

Troubleshooting 57 Action: 1. If power management software is being used, check the log files to obtain specific error information to help identify

Strany 54 - Power management 54

Troubleshooting 58 b. Remove one or more load devices to reduce the power requirements. c. Wait at least 5 seconds and restart the UPS. d. If the

Strany 55 - Troubleshooting

Troubleshooting 59 Overtemperature condition Possible cause: The UPS internal temperature is too high, or a fan has failed. Action: 1. Power down t

Strany 56 - UPS is in Auto-Bypass mode

Contents 6 Preventing electrostatic discharge ...

Strany 57 - General alarm condition

Troubleshooting 60 Checksum failure error A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM map whil

Strany 58 - UPS is on battery

Specifications 61 Specifications UPS physical specifications Parameter Value Height 8.9 cm (3.5 in) Depth 63.5 cm (25 in) Width 44.5 cm (17.5 i

Strany 59 - Overload condition

Specifications 62 UPS model Load segment Output receptacles — — 1 x L6-20R — 2 3 x IEC-320-C13 — — 1 x IEC-320-C19 R/T3000 INTL 1 3 x IEC-320-

Strany 60

Specifications 63 Feature Specification Charging Complete charge takes no more than 48 hours. After approximately 3 hours, the batteries reach 80%

Strany 61 - Specifications

Spares 64 Spares Ordering spares To order a spare, visit the HP website (http://www.hp.com/buy/parts). To replace parts under warranty, contact an H

Strany 62 - Battery specifications

Spares 65 ERM spare parts list Item Description Spare part number 1 ERM unit 517702-001 2 UPS/ERM mounting brackets* 582931-001 3 Mounting r

Strany 63 - REPO port specifications

Support and other resources 66 Support and other resources Before you contact HP Be sure to have the following information available before you call

Strany 64 - UPS spare parts list

Warranty information 67 Warranty information Limited warranty To back up the wide range of features offered with the UPS, a 3-year limited warranty

Strany 65 - Hardware options

Warranty information 68 Recommended duration of use Although tests and a multitude of customer experiences have shown no noticeable performance issu

Strany 66 - Support and other resources

Regulatory compliance notices 69 Regulatory compliance notices Regulatory compliance identification numbers For the purpose of regulatory compliance

Strany 67 - Warranty information

Component identification 7 Component identification UPS R/T3000 G2 overview The HP UPS R/T3000 G2 features a 2U rack-mount with convertible tower de

Strany 68 - Recommended duration of use

Regulatory compliance notices 70 radio communications. However, there is no guarantee that interference will not occur in a particular installation.

Strany 69 - FCC rating label

Regulatory compliance notices 71 This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. C

Strany 70 - Modifications

Regulatory compliance notices 72 This symbol on the product or on its packaging indicates that this product must not be disposed of with your other

Strany 71 - • EMC Directive 2004/108/EC

Regulatory compliance notices 73 Class B equipment Chinese notice Class A equipment Battery replacement notice WARNING: Power products conta

Strany 72 - Korean notice

Regulatory compliance notices 74 Power cord statement for Japan

Strany 73 - Battery replacement notice

Electrostatic discharge 75 Electrostatic discharge Preventing electrostatic discharge To prevent damaging the system, be aware of the precautions yo

Strany 74

Acronyms and abbreviations 76 Acronyms and abbreviations EEPROM electrical erasable programmable read only memory ERM extended runtime module IEC

Strany 75 - Electrostatic discharge

Documentation feedback 77 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat

Strany 76 - Acronyms and abbreviations

Index 78 A alarms, silencing 44 authorized reseller 66 Auto-Bypass mode 41, 56 B backup time, insufficient 60 batteries, care and storage

Strany 77 - Documentation feedback

Index 79 HP technical support 66 I input specifications 61 input voltage is out of range 58 installation instructions 13, 17, 26, 32, 35 ins

Strany 78 - Index 78

Component identification 8 UPS front panel controls Item Description Function 1 Test/Alarm Reset button Silences UPS alarms ("Silenc

Strany 79 - Index 79

Index 80 system configuration settings 42 T Taiwan battery recycling notice 73 technical support 66 telephone numbers 66 temperature ranges

Strany 80 - Index 80

Component identification 9 The front panel is shown with the bezel removed. Item LED description Load level 1 Self Test On—The load level

Komentáře k této Příručce

Žádné komentáře