Web interface 17
Indicators Meaning
Actual web interface alarm
message
Temperature too low
Condition Average server air temperature is lower than the temperature assigned in
the web interface Intake Temp tab (on page 24) Low Temperature
Threshold field
Sensors Air temperature sensor
SNMP notification Warning
Type of message Warning
Solution:
1. Verify water flow matches specifications required for heat load.
2. Verify whether the water temperature is below the expected range.
3. Adjust the temperature assigned in the web interface Intake Temp tab (on page 24) Low
Temperature Threshold field.
4. Contact your building supervisor.
Temperature above threshold (Warning Temperature Threshold field)
Indicators Meaning
Actual operator display alarm
message
Temperature Too high
Actual web interface alarm
message
Temperature too high
Condition Average server air temperature is above the temperature assigned in the
web interface Intake Temp tab (on page 24) Warning Temperature
Threshold field
Modules or sensors Air temperature sensor
SNMP notification Warning
Type of message Warning
Solution:
1. Verify water flow matches specifications required for heat load.
2. Verify whether the water temperature is above the expected range.
3. Adjust the temperature assigned in the web interface Intake Temp tab (on page 24) Warning
Temperature Threshold field.
4. Contact your building supervisor.
Emergency Door Opening due to Water Flow Loss (0 l/min; 36/34/35°C) (0 gal/min; 97/93/95°F)
Indicators Meaning
Actual operator display alarm
message
Emergency Door, Flow