Cooling performance parameter settings 45
Parameter Function
Warning
Temperature
Threshold
Used to issue a warning if the warning temperature
threshold temperature is exceeded
Low Temperature
Threshold
Used to issue a warning if the low temperature threshold
temperature is exceeded
Water Flow Loss
Emergency Door
Opening
Temperature
Threshold
Used to open the MCS doors when the temperature
threshold is exceeded and water loss is detected
This value cannot be lower than 5°C (9°F) above or
more than 20°C (36°F) above the Server Intake
Temperature Set Point.
High Temperature
Emergency Door
Opening Threshold
Used to open the MCS doors when the temperature
threshold is exceeded
This value:
Cannot be lower than 5°C (9°F) above or more than
20°C (36°F) above the Server Intake Temperature
Set Point.
Cannot be less than the Water Flow Loss Emergency
Door Opening Temperature Threshold.
Excessive
Moisture:
Condensation
Pump Cycles
Warning
Threshold
Used to issue a warning if the condensation pump
exceeds the permissible number of cycles within a 24-
hour period
Excessive
Moisture:
Condensation
Pump Running
Time Warning
Threshold
Used to issue a warning if the condensation pump has
run longer than the permissible running time
Alarm Relay Used to enable or disable the alarm relay
Audible Alarm Used to enable or disable the audible alarm
Alarm Reset Used to enable the alarm to be reset automatically (Auto)
or manually (Manual)
Trap Receiver Used to activate trap receivers 1 through 4
Server Intake
Temperature Trap
Message Text
Used to enter information that displays when a server
intake temperature trap is received