Strana 1 - Planning Manual

3PAR InServ ® E-Class/F-Class Storage Server Physical Planning Manual 3PAR Inc. 4209 Technology Drive Fremont, CA 94538 U.S.A. Part No. 320–200120 Rev…

Strana 2

Revision Notice This is the sixth release of this manual. A complete revision history is provided at the end of this manual. Changes The material in…

Strana 3 - Japanese Compliance Statement

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits…

Strana 5 - Table of Contents

v Table of Contents 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Table of Contents 1 Introduction 1.1 Audience 1.2 1.2 Related…

Strana 6 - 5 Power Requirements

vi Table of Contents 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 3.2.2 Planning for Installation 3.3 3.2.3 Preparing a…

Strana 7

vii Table of Contents 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.3 Electrical Requirements and Limitations 5.7 5.3.1 Power…

Strana 8 - RH Revision History

viii Table of Contents 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7 Third-Party Rack Mounting 7.1 Introduction 7.1 7.2 Third…

Strana 9 - Introduction

1 Introduction In this chapter 1.1 Audience 1.2 1.2 Related Documentation 1.2 1.3 Organization 1.3 1.4 Typographical Conventions 1.4 1.5 Advisories…

Strana 10 - 1.2 Related Documentation

2 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 1.1 Audience The information in this manual is intended for use by 3PAR…

Strana 11 - 1.3 Organization

3 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 1.3 Organization This manual is organized as follows: Chapter 1, Introduction…

Strana 12 - 1.4 Typographical Conventions

4 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 1.4 Typographical Conventions The following typographical conventions are used…

Strana 13 - 1.5 Advisories

5 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 1.5 Advisories Before installing an InServ Storage Server, consult Appendix A…

Strana 15 - Specifications

1 System Components and Specifications 2 System Components and Specifications In this chapter 2.1 Introduction 2.1 2.2 3PAR InServ Storage Server…

Strana 16

2 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 2.2 3PAR InServ Storage Server Components 3PAR Utility Storage systems are based…

Strana 17

3 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 2-1 and Figure 2-2 on page 2.4 show the front and rear views of a fully…

Strana 18

4 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 2-2. The Rear View of an F400 Storage Server with 4 Controller Nodes…

Strana 19 - 2.3 Physical Dimensions

5 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 2.3 Physical Dimensions Table 2-1 lists the physical dimensions for the E-Class…

Strana 20

6 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Maximum Load per leveling Foot 111 lbs/sq. in. 50.5 kg/sq. cm E200 Controller…

Strana 21

7 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Weight: 4 Controller Nodes (fully populated) 160 lbs. 72.6 kg Drive Chassis…

Strana 22 - 2.4 System Capacity

8 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 2.4 System Capacity Table 2-2 lists system capacity specifications for the…

Strana 23

9 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual RAID 5 data to parity ratios 2:1, 8:1 RAID 6 data to parity ratios 6:2, 14:2…

Strana 24

10 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 2.5 Power and Heat Specifications Table 2-3 describes electrical current…

Strana 25

11 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 2 Meter Cabinet Max. Watts per Cabinet (fully populated) * 5,580 Max. BTUs/hour…

Strana 26

12 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual E200 Controller Node Chassis Watts 730 BTUs/hour (fully populated) 2491…

Strana 27

13 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual F400 Controller Node Chassis (Quad Node) Watts 1460 BTUs/hour (fully populated)…

Strana 28

14 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Drive Chassis Watts 525 BTUs/hour (fully populated) 1,792 BTUs/hr. Input…

Strana 29 - ‡ Under maximum load

15 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4 x 1 TB NL Drives Watts 47 32 BTUs/hour 160 109 Service Processor Supermicro…

Strana 30

16 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 2.6 Environmental Specifications Table 2-4 lists the environmental…

Zobrazit všech 144 stran
Strana 31

17 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Relative humidity 20–80 percent non-condensing, maximum gradient 10 percent per…

Strana 32 - 2.7 Cable Specifications

18 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 2.7 Cable Specifications Table 2-5 identifies the types of cables commonly…

Strana 33 - General Site Planning

1 General Site Planning 3 General Site Planning In this chapter 3.1 Introduction 3.1 3.2 General Planning 3.2 3.2.1 Customer Responsibilities 3.2…

Strana 34 - 3.2 General Planning

2 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 3.1 Introduction This chapter provides general recommendations for physical…

Strana 35

3 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Adequate power is necessary for the reliable functioning of electronic equipment…

Strana 36

4 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 3.2.3 Preparing a Pre-Installation Site Planning Guide Prior to installation…

Strana 37 - 3.3.1 Shipping Requirements

5 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 3.3 Shipping and Acclimatization Requirements Safe transport of InServ Storage…

Strana 38

6 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 3.3.2 InServ Storage Server Cabinet Shipping Containers A separate crate holds…

Strana 39

7 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual When the equipment arrives, you must make sure that there is enough room to…

Strana 40

8 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 3.3.2.1 Cabinet Shipping Container (2 Meter) Measurements for the shipping…

Strana 41

9 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual The equipment is removed from the front of the container by pulling on two…

Strana 42 - Rotary Latch (4x)

10 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Wooden cabinet crate (one per 1M rack cabinet): 52 5/8 in. (133.7 cm) x 34 in.…

Strana 43 - 3.3.3 Acclimatization

11 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 3.3.3 Acclimatization InServ Storage Servers shipped or stored at extreme…

Strana 45 - Considerations

1 Structural/Environmental Considerations 4 Structural/Environmental Considerations In this chapter 4.1 Introduction 4.2 4.3 Establishing the Proper…

Strana 46 - 4.2 General Information

2 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.1 Introduction This chapter discusses the placement, housing and environmental…

Strana 47

3 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.3 Establishing the Proper Foundation As with any electronic equipment that…

Strana 48

4 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.3.2 Raised Floor Requirements There are additional structural considerations…

Strana 49 - Vented Tiles

5 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Placing each storage server cabinet across two floor tiles is strongly…

Strana 50

6 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual When placing cabinets with their weight shared by the same panels as shown in…

Strana 51

7 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.3.4 Tile Cutout Specifications Figure 4-3 defines the recommended tile cutout…

Strana 52 - All Dimensions in Millimeters

8 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.3.5 Anchoring Dimensions for InServ Storage Servers Some installations may…

Strana 53

9 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 4-6. Bottom View Dimensions for the InServ Storage Server Leveler Foot…

Strana 54

10 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.3.6 Additional Flooring Recommendations Consider the following…

Strana 55 - 0061_T_R1

11 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual The resistance between adjacent tiles should not be less than 150 kilohms when…

Strana 56

12 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual A cold aisle has perforated floor tiles or grates that enable cold air to rise…

Strana 57

13 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual When establishing an operating site for an InServ storage server, provide for…

Strana 58

14 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.5 Meeting Environmental Conditions For the 3PAR InServ Storage Servers, it is…

Strana 59

15 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.5.1 Maintaining the Optimal Temperature The level of cooling required for the…

Strana 60

16 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual for any period negatively affects the system’s reliability and performance, and…

Strana 61 - 4.5.3 Air Cleanliness

17 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual The air-conditioning units should have controls monitoring under the floor…

Strana 62

18 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Metal flakes or filings, such as those produced by sawing, filing, or drilling.…

Strana 63 - 4.5.4 Minimizing Vibration

19 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 4.5.4 Minimizing Vibration The E-Class/F-Class Controller Chassis have been…

Strana 65 - Power Requirements

1 Power Requirements 5 Power Requirements In this chapter 5.1 Introduction 5.2 5.2 Powering InServ Storage Servers 5.2 5.2.1 Power Distribution Units…

Strana 66 - 5.1 Introduction

2 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.1 Introduction This chapter defines the general power requirements for the…

Strana 67

3 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 5-1. Power Supplies Within the Power Domains 3PAR cabinets contain four…

Strana 68

4 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Storage server PDUs are equipped with NEMA® L6–30 or IEC 60309 connectors…

Strana 69

5 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.2.1 Power Distribution Units (PDUs) For each cabinet, the four Power…

Strana 70 - 5.2.2 Power Cord Connections

6 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.2.2 Power Cord Connections 3PAR InServ Storage Servers arrive with all…

Strana 71

7 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.3 Electrical Requirements and Limitations Before physically installing an…

Strana 72

8 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Max. BTUs/hour per cabinet (fully populated) 9,825 Input Voltage (VAC) (200…

Strana 73

9 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Watts 730 BTUs/hour (fully populated) 2491 BTUs/hr Input Voltage 100-240 VAC…

Strana 74

10 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Supermicro BTUs/hour (fully populated) 1370 BTUs/hr. Supermicro II Watts 280…

Strana 75 - 5.3.2 Voltage Requirements

11 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.3.2 Voltage Requirements The following are the voltage requirements for the…

Strana 76 - 5.4 Power Quality

12 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Table 5-3 lists total current limitations for storage server systems depending…

Strana 77 - 5.7 Electrostatic Discharge

13 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.5 Voltage and Frequency Tolerance Steady state voltage must be maintained…

Strana 78 - 5.10 Redundant Power

14 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5.8 Branch Circuits The individual panel branch circuits should be protected by…

Strana 79

15 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual InServ Storage Servers with 3PAR cabinets support redundant power within the…

Strana 80 - (Front View)

16 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 5-5. Front View of the Power Domains Within the Controller Nodes and…

Strana 81 - (Rear View)

17 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 5-6. Rear View of the Power Domains Within the Controller Nodes and…

Strana 82 - Drive Chassis 4

18 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 5-7 and Figure 5-8 illustrate standard redundant power configurations…

Strana 83

19 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 5-8. Redundant Power Configuration E200 (1M) 0390_L_R4 Drive Chassis 0…

Strana 84

20 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 5-9 and Figure 5-10 illustrate standard redundant power configuration…

Strana 85

21 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 5-10. Redundant Power Configuration F400 (2M) Top Cable Routing Access…

Strana 87 - Connectivity

1 Network, Cabling and Connectivity 6 Network, Cabling and Connectivity In this chapter 6.1 Introduction 6.2 6.2 Planning Network Access 6.2 6.2.1…

Strana 88 - 6.2 Planning Network Access

2 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.9.1 Connecting the Service Processor 6.24 6.1 Introduction This chapter…

Strana 89 - 6.2.1.1 Shared Network

3 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.2.1.1 Shared Network With a shared network topology, the storage server and…

Strana 90 - 6.2.1.2 Split Network

4 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.2.1.2 Split Network With a split network topology, the storage server is on…

Strana 91 - 6.2.1.3 Private Network

5 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Two Ethernet connections from the private network segment to the storage server…

Strana 92

6 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual At least one management station on the private network segment. 6.3 Adapter…

Strana 93 - 6.3.1 E-Class Controller Node

7 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.3.1 E-Class Controller Node As shown in Figure 6-4, for the E200 node, there…

Strana 94 - 6.3.2 F-Class Controller Node

8 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.3.2 F-Class Controller Node As shown in Figure 6-5, for the F-Class node…

Strana 95

9 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.3.3 Controller Node Slot Loading Order Table 6-1 shows the controller slot…

Strana 96 - 6.3.3.1 Slotting Rules

10 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.3.3.1 Slotting Rules When configuring an F-Class with FC adapters, there are…

Strana 97 - 6.3.5 Host Connections

11 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.3.4 Drive Chassis Connections The following guidelines should be followed for…

Strana 98 - 6.4 TCP/IP Port Assignments

12 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.4 TCP/IP Port Assignments Table 6-2 describes the TCP/IP port assignments for…

Strana 99

13 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 162: SNMPTRAP Used by the 3PAR SNMP agent to send unsolicited alerts as SNMPv2c…

Strana 100 - ■ 3PAR Service Processor

14 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5782: 3PAR Management Service (unsecured) Used for InServ monitoring and…

Strana 101

15 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5783: 3PAR Management Service with SSL (secured) Used for InServ monitoring and…

Strana 102

16 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 5988: WBEM CIM-XML (HTTP) (unsecured) Used for InServ monitoring and…

Strana 103 - 6.5 Required Cables

17 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.5 Required Cables The quantities and lengths of the cables required for…

Strana 104

18 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.6 External Cable Connections Table 6-4 includes specific guidelines for…

Strana 105

19 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Each controller node supports one Ethernet connection to a switch or hub.…

Strana 106

20 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.7 Internal Cable Connections For storage servers housed in single cabinets…

Strana 107 - Lower Access

21 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.8 Cable Routing Options Typical storage server cabinets have both upper and…

Strana 108 - Eth-0 (Ext)

22 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.9 Service Processor Connections The Service Processor provides remote error…

Strana 109

23 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Table 6-7 summarizes the connectivity options for both data transfer and remote…

Strana 110

24 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 6.9.1 Connecting the Service Processor The service processor uses…

Strana 111 - Third-Party Rack Mounting

1 Third-Party Rack Mounting 7 Third-Party Rack Mounting In this chapter 7.1 Introduction 7.1 7.2 Third Party Rack Mounting Considerations 7.2 7.3…

Strana 112 - 7.3 Dimensional Requirements

2 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7.2 Third Party Rack Mounting Considerations Some installations may want to use…

Strana 113

3 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 7-1. Required Dimensions for the InServ E200/F200 and the F400 Node…

Strana 114 - (All Measurements in Inches)

4 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 7-2. Required Dimensions for the DC3 Drive Chassis 19.000 17.650 5.066…

Strana 115

5 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual If you are installing the 3PAR equipment in a Four Post Cabinet, it must meet…

Strana 116

6 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7.3.1 Rack Space Considerations 3PAR highly recommends installing node-chassis…

Strana 117 - 7.3.2 RETMA Rail Spacing

7 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7.3.2 RETMA Rail Spacing The Radio Electronics Television Manufacturers…

Strana 118

8 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7.3.3 Maintaining Minimum Clearances Proper clearances should be maintained for…

Strana 119

9 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual Figure 7-6 shows the minimum clearances that should be reserved for the 2 post…

Strana 120 - 7.4.1 Two-Post Shelf Kit

10 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7.4 Rack Mounting Kits There are two different rack-mounting kits available to…

Strana 121 - 7.4.2 Four-Post Shelf Kit

11 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7.4.1.2 Flush Mounting Flush-mount shelves are mounted on the back of the…

Strana 122

12 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual 7.5 Redundant Power Requirements Each InServ Storage Server component is…

Strana 123 - Statements

Agency Compliance Statements A Agency Compliance Statements In this appendix A.1 Safety Precautions A.2 A.2 Safety Agency Compliance Notices A.2 A.2.1…

Strana 124 - A.1 Safety Precautions

A.1 Safety Precautions To be safe and to protect system data and equipment, always follow the instructions in this manual when installing…

Strana 125

WAARSCHUWING: Deze eenheid dient te worden geïnstalleerd op een beperkt toegankelijke locatie. ADVERTENCIA: Está unidad deberá ser instalada en una…

Strana 126

For storage servers with 3PAR cabinets, secure the system by locking the rear doors on all cabinets. WARNING: Hazardous energy is located behind the…

Strana 127

A.2.2 Battery Replacement and Disposal Storage server controller nodes contain 3-V lithium coin batteries. These batteries require periodic…

Strana 128

ADVERTENCIA: Existe el peligro de explosión si la batería de litio dentro del controlador del nodo es reemplazada incorrectamente. Reemplacela…

Strana 129

VORSICHT: Gebrauchte Batterien nur gemäß Herstelleranweisung entsorgen. ATTENTION: Débarrassez-vous des batteries use selon les instructions de…

Strana 130 - A.2.3 Controller Nodes

A.2.3 Controller Nodes For controller nodes installed in cabinets not provided by 3PAR, observe the following precautions: WARNING: Install this unit…

Strana 131

WARNING: Hazardous energy located on rear connectors. ACHTUNG: An den rückwärtigen Anschlüssen liegen gefährliche Spannungen an. AVERTISSEMENT…

Strana 132

ADVERTENCIA: Energía peligrosa localizada en los conectores traseros. WARNING: There is danger of an explosion if the lithium coin battery inside the…

Strana 133

AVERTISSEMENT: Il y a un danger d'explosion si la batterie de lithium à l'intérieur du contrôleur est incorrectement positionnée. Remplacez la…

Strana 134

CAUTION: Dispose of used batteries according to the manufacturer’s instructions. VORSICHT: Gebrauchte Batterien nur gemäß Herstelleranweisung…

Strana 135 - A.2.4 Drive Chassis

A.2.4 Drive Chassis For drive chassis installed in cabinets not provided by 3PAR, observe the following precautions: WARNING: Install this unit in a…

Strana 136

WARNING: There is danger of an explosion if the battery is incorrectly replaced. Replace only with the same or equivalent type recommended by the…

Strana 137

WAARSCHUWING: Er bestaat kans op een explosie als de batterij niet op de juiste wijze wordt vervangen. Alleen te vervangen door een type dat…

Strana 138 - A.3 3PAR Power Cables

A.3 3PAR Power Cables English Compliance Statement All power cables provided by 3PAR are for exclusive use for 3PAR products. Japanese Compliance…

Strana 139

IX.1 Index A access recommendations, physical 4.13 altitude requirements and specifications 2.16, 4.14 audience, for this manual 1.2 authorized…

Strana 140

IX.2 Index 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual structural requirements 4.4 to 4.6 H humidity specifications for…

Strana 141

IX.3 Index 3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual W weight and load for server 4.6

Strana 142

IX.4 Index

Strana 143 - Revision History

RH.1 Revision History Release Level Revision Summary 320-200120 Rev A March 2009 First version of this manual to accommodate physical planning for the…