Physical Planning Manual

Abstract
This manual provides information that is useful for planning and preparing for the installation of HP 3PAR S-Class and T-Class
Storage systems. Use this document in conjunction with the
HP 3PAR Systems Assurance and Pre-Installation Site Planning Guide
that details specific system configuration and installation information for your storage system and operating site. The information
in this manual is intended for use by HP customers, in conjunction with the advice and assistance of an HP Sales Representative
or Systems Engineer, for the purpose of planning an HP 3PAR Storage system installation. The installation of HP 3PAR Storage
systems and hardware components is to be completed by qualified technicians who are authorized by HP. Authorized technicians
include HP Field Engineers, Value Added Resellers (VARs), and authorized third-party field technicians.
HP Part Number: QL226-97055
Published: September 2013
Edition: 1

Soubor PDF · ·

Tisk

Tisknout dokument

Sdílení

Shrnutí obsahu

Strana 1 - Physical Planning Manual

HP 3PAR S-Class/T-Class Storage System Physical Planning Manual Abstract This manual provides information that is useful for planning and preparing…

Strana 2

© Copyright 2013 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties…

Strana 3 - Contents

Contents 1 System Components and Specifications 5 HP 3PAR Storage System Components 5 S400/S800 HP 3PAR Storage System Specifications 7 Physical…

Strana 4 - 4 Contents

Supported Network Topologies 37 Shared Network 37 Private Network 38 TCP/IP Port Assignments 39 Fibre Channel Connections 41 Required Cables 43…

Strana 5

This chapter provides detailed system specifications for the HP 3PAR S-Class and T-Class Storage systems and serves as a quick reference for other…

Strana 6

Figure 1 The Front of an S-Class or T-Class HP 3PAR Storage System

Strana 7 - Physical Specifications

Figure 2 The Rear View of an S-Class or T-Class HP 3PAR Storage System S400/S800 HP 3PAR Storage System Specifications HP 3PAR S400 and S800 Storage…

Strana 8 - Capacity Specifications

Table 1 S400/S800 Storage System Physical Specifications (continued) S400/S800 Storage System Physical Specifications 223.4 kg492.5 lbs.Maximum Weight…

Strana 9

T400/T800 HP 3PAR Storage System Specifications HP 3PAR T400 and T800 Storage systems accommodate up to four or eight controller nodes, respectively.…

Strana 10 - Power and Heat Specifications

Table 4 T400/T800 Storage System Capacity Specifications (continued) T800T400Feature 6:2, 14:26:2, 14:2RAID 6 data to parity ratios 50 GB SSD, 146 GB…

Strana 11 - Environmental Specifications

Table 5 T-Class Storage System Power Requirements (continued) 160208BTUs/hour 4 x 450 GB FC Drive Magazines 5788Watts 194300BTUs/hour 4 x 600 GB FC…

Strana 12 - Cable Specifications

Table 6 Environmental Specifications for HP 3PAR Storage systems (continued) ValueSpecification 0–3,000 ft (914.4 m) 50 –95° F (10 –35° C)…

Strana 13

This chapter provides general recommendations for physical planning and site preparation for installation and operation of the HP 3PAR S-Class and…

Strana 14 - Shipping Requirements

Verify that electrical service wiring has been installed at the server’s predetermined location. Refer to the respective product specifications for…

Strana 15 - Cabinet Shipping Container

package for obvious damage or signs of tampering and notify both HP and the carrier of any issues. Shipping container measurements are as follows…

Strana 16

Figure 4 Front View of the Cabinet Shipping Container The equipment is removed from the front of the container by pulling on two straps that wrap…

Strana 17 - Acclimatization

Figure 5 Front View of the Container with Ramp Down Acclimatization HP 3PAR Storage systems shipped or stored at extreme temperatures may require time…

Strana 18 - Raised Floor Requirements

You should consider the following when choosing or designing your facilities for HP 3PAR Storage systems: Equipment location and layout that allows…

Strana 19

Table 10 Raised Floor Specifications ValueSpecification Less than 0.06 in. (1.5 mm) Less than 0 .10 in. (2.5 mm) Flatness tolerance Per 10 ft (3 m)…

Strana 20 - Tile Cutout Specifications

However, before placing a cabinet on floor tiles shared with other cabinets or equipment, first verify that the floor panels can tolerate the weight…

Strana 21

Figure 8 Tile Cutout Specifications WARNING! To prevent potential collapse, loaded floor panels that have cutouts to facilitate cable routing may…

Strana 22

Figure 9 Front View Dimensions for the HP 3PAR Storage System Figure 10 Side View Dimensions for the HP 3PAR Storage System Figure 11 Bottom View…

Strana 23

Additional Flooring Recommendations Consider the following recommendations for raised floor installations: The flooring should be high enough to allow…

Strana 24 - Providing for Service Access

Figure 12 Hot-Aisle/Cold-Aisle Layout Form rows of racks or cabinets perpendicular to air conditioners. This formation facilitates an unobstructed…

Strana 25

NOTE: The S800 and T800 Storage systems have circuit breakers located at both the front and rear of the system. It is necessary to maintain access to…

Strana 26 - Air Supply and Flow

percent of the load, whereas the dry heat of electronic equipment produces a sensible heat ratio of over 95 percent. Prior to installation, verify…

Strana 27 - Air Cleanliness

recommendations for outside air in comfort air-conditioning are 10 to 15 percent of the airflow, the computer room environment is cleaner and operates…

Strana 28

This chapter describes the general power requirements for the HP 3PAR Storage systems. Powering HP 3PAR Storage Systems The cabinets used to house the…

Strana 29

NOTE: If a storage system cabinet does not have components installed in the top four bays (bays 0–3, or the highest 16U of the cabinet), the two upper…

Strana 30 - Power Cord Connections

Figure 15 Power Banks in the PDU WARNING! To avoid possible injury, damage to storage system equipment, and potential loss of data, do not use the…

Zobrazit všech 53 stran
Strana 31 - Voltage Spikes

NOTE: When routing the power cords through the bottom of the 2 meter cabinet, the usable cord length extends 9.5 to 10 feet away from the cabinet. If…

Strana 32 - Redundant Power

Installing a lightning protection device on the server room power source is recommended when the following conditions exist: The primary power is…

Strana 33 - Redundant Power 33

Figure 17 Front View of the Power Domains Within the Controller Nodes and Drive Chassis Redundant Power 33

Strana 34

Figure 18 Rear View of the Power Domains Within the Controller Nodes and Drive Chassis WARNING! To avoid possible injury, damage to storage system…

Strana 35

Figure 19 Redundant Power Configuration Diagram (S800 and T800) Table 15 Redundant Power Configuration (S800 and T800) AC CordPower BankPDU Number…

Strana 36 - 5-L,6-L23

Table 15 Redundant Power Configuration (S800 and T800) (continued) AC CordPower BankPDU Number 7-R,8-R13 5-L,6-L23

Strana 37 - Planning Network Access

This chapter provides information about determining the best network configuration for the HP 3PAR Storage systems being installed at your site…

Strana 38 - Private Network

Figure 20 Storage System and SP on the Customer Network (Shared Topology) A shared topology requires: A static IP address and system name for the…

Strana 39 - TCP/IP Port Assignments

NOTE: It is strongly recommended that the private network segment also have a management station to communicate with the SP. NOTE: This configuration…

Strana 40

Table 16 TCP/IP Port Usage Table (continued) Flow of TrafficUsagePort Passes unsolicited events from the storage system and is used by the following…

Strana 41 - Fibre Channel Connections

Table 16 TCP/IP Port Usage Table (continued) Flow of TrafficUsagePort HP 3PAR CIM Server 3rd Party CIM Client <--> HP 3PAR CIM Server Not part of an…

Strana 42

Figure 22 S-Class Controller Node Fibre Channel Ports (Dual-Port Adapters) Figure 23 T-Class Controller Node Fibre Channel Ports (Dual-Port Adapters)

Strana 43 - External Cable Connections

Fibre Channel adapters can have either two ports (dual-port adapters ) or four ports (quad-port adapters). Required Cables The quantities and lengths…

Strana 44 - Internal Cable Connections

To provide redundancy and to permit online software upgrades, both controller nodes in a single horizontal node pair (for example, nodes 0 and 1…

Strana 45 - Service Processor Connections

Cable Routing Options Storage system cabinets have both upper and lower access openings available for Fibre Channel cable routing (Figure 24 (page…

Strana 46 - Table 21 SP Connections

Table 21 SP Connections ConfigurationConnection type For SP: connection from the RJ-45 connector in the ETH 0 port at the rear of the SP to an…

Strana 47

Contacting HP For worldwide technical support information, see the HP support website: http://www.hp.com/support Before contacting HP, collect the…

Strana 48

See:For information about: HP 3PAR-to-3PAR Storage Peer Motion GuideMigrating data from one HP 3PAR storage system to another HP 3PAR Secure Service…

Strana 49

See:For information about: Planning for HP 3PAR storage system setup Hardware specifications, installation considerations, power requirements…

Strana 50

HP 3PAR Service Processor Software User Guide: Service Edition Initializing and using the Service Processor HP 3PAR Service Processor Software Upgrade…

Strana 51 - HP 3PAR branding information

Typographic conventions Table 22 Document conventions ElementConvention Bold text Keys that you press Text you typed into a GUI element, such as a…

Strana 52 - 7 Documentation feedback

7 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentation, send any errors…

Strana 53 - A Regulatory information

A Regulatory information For important safety, environmental, and regulatory information, see Safety and Compliance Information for Server, Storage…

Další dokumenty pro Software HP 3PAR

Otázky k HP 3PAR

K tomuto návodu zatím nejsou žádné otázky. Položte první.

Položit otázku

Odpovídáme podle návodu a uvádíme stranu. Otázka se na webu zobrazí po kontrole.

Všechny otázky a odpovědi ›

Související produkty a manuály pro Software HP 3PAR