HP 4100 Enterprise Virtual Array Uživatelský manuál Strana 143

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 180
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 142
Table 53 EVA 6x00 UPS loading (continued)
% of UPS capacity
WattsEnclosures
R12000R5500R3000
7.921.235.39532
4.812.821.45771
Table 54 EVA 4x00 UPS loading
% of UPS capacity
WattsEnclosures
R3000R1500
60.616374
46.694.012603
32.765.98832
18.737.95071
Environmental specifications
Table 55 Environmental specifications
50° to 95° F (10° to 35° C) - Reduce rating by 1° F for each 1000 ft. altitude (1.8°
C/1,000 m)
Operating temperature
-40° to 150° F (-40° to 66° C)Shipping temperature
10% to 90% non-condensingOperating humidity
5% to 90% non-condensingShipping humidity
Up to 8,000 ft. (2,400 m)Altitude
Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron or largerAir quality
Environmental and operating specifications 143
Zobrazit stránku 142
1 2 ... 138 139 140 141 142 143 144 145 146 147 148 ... 179 180

Komentáře k této Příručce

Žádné komentáře