Power requirements and considerations 32
Power quality
Most HP products are designed to operate over a wide range of voltages and frequencies. The products
are tested and shown to comply with certain EMC Specifications. However, damage can occur if these
ranges are exceeded. Severe electrical disturbances can exceed the design specifications of the
equipment.
Factors affecting power quality
Common factors that affect power quality include the following:
Electrical storms
Utility service brownouts or sags
Faults in the power generation equipment
Large inductive loads, such as motors and welders
Load fluctuations occurring within the facility distribution system
Loose connections or other faults in the distribution system wiring
Power system protection
HP products can be protected from the sources of many of these electrical disturbances by using the
following:
A dedicated power distribution system
Power conditioning equipment
Over- and under-voltage protection and detection circuits
Lightning arresters on power cables to protect equipment against electrical storms
The power distribution system is designed to provide immunity to power interruptions. However, testing
cannot conclusively rule out loss of service. Use the following guidelines to provide the best possible
performance of power distribution systems for HP computer equipment:
Dedicated power source—Isolates the power distribution system from other circuits in the facility.
Online uninterruptible power supply (UPS)—Keeps input voltage to devices constant and should be
considered if outages of one-half cycle or more are common.
Auto-start generators–provide backup power to the UPS.
Missing-phase and low-voltage detectors—initiate a transfer of the UPS to generator power when a
severe power interruption occurs. For peripheral equipment, these devices are recommended but
optional.
For each situation, refer to qualified contractors or consultants.
Power considerations
Power is best managed within the rack by the use of one or more rack-mounted PDUs. Depending on the
configuration, it may be necessary or preferable to use multiple PDUs to connect all devices inside the
rack.