Power requirements and considerations 33
Connect each PDU to a dedicated (unshared) branch circuit that is rated for the continuous measured load
of all the equipment connected to it. The total power load for a PDU should not exceed 80 percent of the
branch circuit rating. If a PDU is not used, connect each piece of equipment within the rack to a
dedicated branch circuit.
For additional information, see the HP website http://www.hp.com/og/powercapping
.
Power options
The following table describes the available power options and provide details about those options.
Enclosure part
number
Source
type
Source voltage
(nominal)
Plug or
connector
type
Circuit type Power
receptacle
required
412136-B2x
412133-B2x
3-phase 200 to 220 VAC
line to line (phase to
phase), 3-phase
delta 50Hz/60Hz
NEMA L15-
30p, 3-m
(10-ft) power
cord
30A 200/208V
Three-phase
delta
L15-30R
403318-B2x
403319-B2x
3-phase 346 VAC to 415
VAC line to line
200 VAC to 240
VAC line to neutral
3-phase WYE
IEC 309, 4-
pole, 5-wire,
Red, 3-m
(10-ft) power
cord
16A 346-415V IEC 309, 4-Pole,
5-Wire, red
403320-B2x
403321-B2x
Single-
phase
100V to 120V AC
200V to 240V AC
50Hz/60Hz
IEC 320
C19-C20
1.2-m
(4-ft) jumper
cord
16A Single-
phase 100V to
120V or 200V
to 240V
IEC320-C19*
DC -36 VDC to -72 VDC 6.4mm
(0.25-in)
studs for bolt
down
conections
— 45DG 4AWG
1/4 2H (Two-
hole lug, 45-
degree bend,
6.4-mm (0.25-in)
stud hole size,
16-mm (0.63-in)
hole spacing)
*Additional power cords are available for single-phase solutions. See the HP Website
(http://www.hp.com/go/rackandpower
).
All branch circuits used within a facility must be connected together to form a common ground. All power
sources such as transformers, UPS devices, and other sources, must be connected together to form a
common ground.
NOTE: When wiring a 3-phase enclosure, phase rotation is unimportant. However, the
rotation must be consistent for both plugs.
Power redundancy
High-availability information technology equipment such as servers and storage devices can be
configured with backup or redundant power sources and power supplies in either of the following
configurations: