HP mc-Series 5042 Rack
User Guide
Abstract
This document is for the person who installs racks and rack products. This procedure is performed only by trained personnel.
HP assumes you are
qualified in performing installations and trained in recognizing hazards in rack products.
Part Number: 669044-002
December 2012
Edition: 2
Zobrazit stránku 0
1 2 3 4 5 6 ... 77 78

Shrnutí obsahu

Strany 1 - User Guide

HP mc-Series 5042 Rack User Guide Abstract This document is for the person who installs racks and rack products. This procedure is performed only by

Strany 2

Installation 10 Installing the MCS 5042 unit WARNING: The MCS 5042 unit and rack are shipped together on a heavy duty shock pallet weighing appr

Strany 3 - Contents

Installation 11 6. Plug the network cable into the RJ-45 connector on the transfer switch in the top of MCS 5042 unit. 7. Plug the other end of th

Strany 4 - Contents 4

Installation 12 WARNING: To reduce the risk of electric shock or damage to the equipment: • Do not disable the power cord grounding plug. The gro

Strany 5 - Overview

Installation 13 12. If the rear extension is installed, this step is optional. Using two M6 trilobe flathead screws, secure the two brackets to the

Strany 6 - Unit top view

Installation 14 WARNING: To reduce the risk of electric shock or damage to the equipment: • Do not disable the power cord grounding plug. The gro

Strany 7 - Configuration factors

Installation 15 b. In the password field, enter the password. The default password is Admin. The Main Menu screen appears. 7. Enter the product ID

Strany 8 - Installation

Installation 16 a. From the Main Menu screen, enter 3 Factory Default. The Default Product Identification screen appears. b. To set the product ID

Strany 9 - Required tools

Installation 17 a. From the Main Menu screen, enter 1 Network Configuration. The Menu Network Configuration screen appears.

Strany 10 - Installing the MCS 5042 unit

Installation 18 b. Enter 1 IP Configuration. The IP Configuration screen appears. c. To disable DHCP, enter 4 Enable/Disable DHCP. d. Enter 1 IP

Strany 11 - Installation 11

Installation 19 a. Return to the Main Menu Network Configuration screen. b. Enter 4 Activate Actual Values. c. To reboot, at the prompt, enter y.

Strany 12 - Installation 12

© Copyright 2012 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Strany 13 - Installation 13

Installation 20 c. Click Sign In. 12. Click Setup>Accounts, and then change the default Web Admin and Web User passwords. 13. Click Save Sett

Strany 14

Installation 21 15. Optional: Enter an SSL key. 16. Click Save Settings. 17. To set up your trap receivers, click Setup>Management>Trap Rec

Strany 15 - Installation 15

Installation 22 19. Optional, but HP-recommended: To set up your SNMP managers, click Setup>Management>SNMP Managers. 20. Click Save Setting

Strany 16

Installation 23 c. Click Sign In. 4. Click Setup>Network. a. To disable DHCP, click the radio button. The default setting is enabled. Whenever

Strany 17 - Installation 17

Installation 24 g. Log in to the new IP address. 5. Click Setup>Accounts, and then change the default Web Admin and Web User passwords. 6. Cl

Strany 18

Installation 25 8. (Optional) Enter an SSL key. 9. Click Save Settings. 10. To set up your trap receivers, click Setup>Management>Trap Rece

Strany 19

Installation 26 12. (Optional, but HP-recommended) To set up your SNMP managers, click Setup>Management>SNMP Managers. 13. Click Save Settin

Strany 20

Installation 27 1. Route the water hoses from the HP Hook Up Kit through the floor cut-out, and then use a hose wrench to install each main hose to

Strany 21

Installation 28 c. Click Sign In. 4. Click Setup>Advanced. 5. In the Temperature Control field, select Manual, and then click Save Settings.

Strany 22

Installation 29 7. Turn on the water by opening the ball valves at the facility water line connections. 8. In the web interface, click the Home ta

Strany 23

Contents 3 Contents Overview ...

Strany 24

Installation 30 10. If necessary, remove trapped air from the heat exchanger by opening the bleeder valve on the top rear side of the cooling unit.

Strany 25

Automatic Door Release Kit 31 Automatic Door Release Kit Automatic Door Release Kit Overview The Automatic Door Release Kit is designed as a safety

Strany 26 - Installation 26

Automatic Door Release Kit 32 To test the Automatic Door Release feature: 1. At the bottom of the screen, click the Door Opening Test button. A new

Strany 27

Management module 33 Management module Management module overview The HP mc-Series 5042 Rack has a management module, which can be accessed remotely

Strany 28

Management module 34 • Fan Module—Displays the Server Intake and Server Exhaust Temperature as well as the RPM of each fan • Water Inlet Temperatu

Strany 29 - Installation 29

Management module 35 Item Reference Description 3 Traffic/link LED Used to display the network connection. • If the LED is green, a 10-MB connec

Strany 30 - Installation 30

Management module 36 2. Enter the password in the password field. The default password is Admin. The Main Menu screen appears. Accessing the manag

Strany 31 - Automatic Door Release Kit

Management module 37 Component Requirement Web browser on a client • Microsoft® Internet Explorer 8.0 • Red Hat Linux operating system (32-bit o

Strany 32

Management module 38 For instructions on changing the password, see the HP mc-Series 5042 Rack Web Interface User Guide. Only one Admin session and

Strany 33 - Management module

Management module 39 Connecting an alarm device to the management module alarm relay An alarm device can be connected to the management module alarm

Strany 34 - Management module components

Contents 4 Environmental specifications ...

Strany 35

Management module 40 Alarm relay item Specification Maximum voltage DC, 24 V internal or DC, 30 V with external power connection

Strany 36 - Web interface requirements

Serial interface 41 Serial interface HP Modular Cooling System Utility overview The HP Modular Cooling System Configuration Utility is used for ente

Strany 37

Serial interface 42 Option number Submenu Description 1 Network Configuration Enter or change network properties for the management modul

Strany 38 - Management module 38

Serial interface 43 IP Configuration submenu Option number Submenu Description 1 IP Address Enter or change the IP address for the managem

Strany 39

Serial interface 44 Change Passwords submenu Option number Submenu Description 1 Console Password 'Admin' Change the Admin pas

Strany 40

Serial interface 45 Info page The Info page displays the following parameters: • IP Address • Subnetmask • Router/Gateway • MAC Address • SysN

Strany 41 - Serial interface

Serial interface 46 Factory Default submenu Option number Submenu Description 1 Set to Factory Default Set the management module to facto

Strany 42 -

Serial interface 47 5. When a connection is established, press Enter and then log in. The Main menu for the management module appears. Follow the on

Strany 43 - IP Configuration submenu

Operator display 48 Operator display Operator display overview The operator display provides information on the system operation, viewable on the ou

Strany 44 - Change Passwords submenu

Operator display 49 Indicators Meaning Type of message Warning Solution: 1. Remove the fan unit. 2. Reinstall the same fan unit. If the warning

Strany 45 - Info page

Overview 5 Overview Introduction The HP mc-Series 5042 Rack is an air and water heat exchanger that removes high levels of excess heat generated by

Strany 46 - Configuring HyperTerminal

Operator display 50 Solution: Verify the water supply. Water temperature input is out of range Indicators Meaning Operator display alarm message W

Strany 47 - Configuring Minicom

Operator display 51 1. Verify the water supply. 2. Contact HP, or see the HP website (http://www.hp.com). Water flow valve is closed Indicators M

Strany 48 - Operator display

Operator display 52 Indicators Meaning Operator display alarm message Temperature too high Web interface alarm message Temperature too high Condit

Strany 49

Operator display 53 Temperature below threshold (Low Temperature Threshold field) Indicators Meaning Operator display alarm message Temperature to

Strany 50

Operator display 54 Indicators Meaning SNMP notification Critical Type of message Alarm Solution: 1. Verify the water supply and that the MCS 504

Strany 51

Operator display 55 Indicators Meaning Condition The water level has exceeded the permissible level of the condensation pump sensor. Modules or sen

Strany 52

Operator display 56 NOTE: To clear the condensation pump cycles warning, click Cooling System in the left navigation frame to access the Cooling

Strany 53

Frequently asked questions 57 Frequently asked questions HP mc-Series 5042 Rack frequently asked questions Question Answer What cooling capacity r

Strany 54

Frequently asked questions 58 Question Answer Is water prevented from entering the MCS 5042 unit if a pipe breaks? Yes, the MCS 5042 unit is physic

Strany 55

Troubleshooting 59 Troubleshooting HP mc-Series 5042 Rack troubleshooting Issue Resolution The water flow is low or not flowing. For more informat

Strany 56

Overview 6 Item Reference 7 Heat exchanger unit 8 Fan units 9 Management module Unit top view NOTE: For easier viewing, the canopies were re

Strany 57 - Frequently asked questions

Specifications 60 Specifications MCS specifications Item Specification Voltage 208/230 VAC +/- 10%, 50/60 Hz Maximum height (including the rack) 2

Strany 58 - Question Answer

Specifications 61 Thermal and air flow performance Maximum thermal and air flow performance parameters Single rack Dual rack (Specification per r

Strany 59 - Troubleshooting

Replaceable parts and maintenance and service information 62 Replaceable parts and maintenance and service information Obtaining replaceable parts F

Strany 60 - Specifications

Water quality and leveling requirements, and condensation management 63 Water quality and leveling requirements, and condensation management Water q

Strany 61 - Environmental specifications

Water quality and leveling requirements, and condensation management 64 Parameter Range Corrosion inhibitor Recommended If your water is out of ra

Strany 62 - Maintenance and service

Water quality and leveling requirements, and condensation management 65 Condensation management Any condensation that forms is collected in each ind

Strany 63

Support and other resources 66 Support and other resources Before you contact HP Be sure to have the following information available before you call

Strany 64 - Leveling requirements

Support and other resources 67 providers or service partners) identifies that the repair can be accomplished by the use of a CSR part, HP will ship

Strany 65 - Condensation management

Support and other resources 68 Pour plus d'informations sur le programme CSR de HP, contactez votre Mainteneur Agrée local. Pour plus d'in

Strany 66 - Support and other resources

Support and other resources 69 HINWEIS: Einige Teile sind nicht für Customer Self Repair ausgelegt. Um den Garantieanspruch des Kunden zu erfüllen,

Strany 67

Configuration factors 7 Configuration factors Optimum environment and site preparation CAUTION: Contaminated water might cause decreased cooling

Strany 68 - Customer Self Repair

Support and other resources 70 sustituciones que lleve a cabo el cliente, HP se hará cargo de todos los gastos de envío y devolución de componentes

Strany 69

Support and other resources 71 Opcional – Peças cujo reparo feito pelo cliente é opcional. Essas peças também são projetadas para o reparo feito pel

Strany 70 - Reparo feito pelo cliente

Support and other resources 72

Strany 71

Support and other resources 73

Strany 72

Regulatory compliance notices 74 Regulatory compliance notices Safety and regulatory compliance For safety, environmental, and regulatory informatio

Strany 73

Acronyms and abbreviations 75 Acronyms and abbreviations CSR Customer Self Repair DHCP Dynamic Host Configuration Protocol MCS modular cooling sys

Strany 74

Documentation feedback 76 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat

Strany 75 - Acronyms and abbreviations

Index 77 A accessing the management module 35, 36 alarm relay 39 Alarms and warnings 48 authorized reseller 66 Automatic Door Release Kit

Strany 76 - Documentation feedback

Index 78 spares 62 specifications 60, 61 specifications, environmental 60 support 66 T technical support 66 telephone numbers 66 Tempera

Strany 77 - Index 77

Installation 8 Installation MCS 5042 kit contents • HP mc-Series 5042 Rack unit installed on an HP Rack (1) • Automatic Door Release kit (1) • Re

Strany 78 - Index 78

Installation 9 Hardware kit contents If any of the following items are missing or damaged, contact your HP authorized reseller. Item Description