Maintenance 84
3.
Remove the two screws securing the X-Slot Card and slide the card out.
To replace the component, reverse the removal procedure.
NOTE: Replacing the HP Management Module might require power management software to be
restarted or reconfigured.
Configuring the Parallel UPS Card
1. Unpack the Parallel UPS Card, and be sure that the card was not damaged during shipment.
NOTE: If installing another X-Slot card, be sure to install the Parallel UPS Card in X-Slot
Communication Bay 2.
2. Remove the UPS X-Slot communication bay cover, and retain the screws.
3. Set the jumper pins on the Parallel UPS Card according to the parallel configuration.
For three or more paralleled UPSs:
o Set the cards of the first and last UPS to Pins 1 and 2.
Zobrazit stránku 83