Hp StorageWorks Scalable File Share Uživatelský manuál Strana 137

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 362
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 136
Verifying the system 6–7
c. Look at the server and confirm that the power has been turned off. Only one server in the system
should be turned off at this point.
d. Turn on the power to the server, as follows:
sfs> boot server south2
e. Use the show server command to verify that the power to the server has been turned on, as
follows:
sfs> show server south2
Name: south2
Primary Role: mds
Backup Server: south1
.
.
.
Power: on
.
.
.
Repeat these steps for each server except the administration server.
3. When you have confirmed that the power management is working correctly for the MDS server and
all of the Object Storage Servers, verify that the power management is working correctly for the
administration server by performing the following steps, where south1 is the administration server:
a. Log in to the MDS server.
b. Turn off the power to the administration server, as follows:
sfs> shutdown server south1 wait=0
c. Use the show server command to verify that the power to the administration server has been
turned off, as follows:
sfs> show server south1
Name: south1
Primary Role: adm
Backup Server: south2
.
.
.
Power: off
.
.
.
d. Look at the server and confirm that the power has been turned off. Only one server in the system
should be turned off at this point.
e. Turn on the power to the administration server, as follows:
sfs> boot server south1
f. Use the show server command to verify that the power to the administration server has been
turned on, as follows:
sfs> show server south1
Name: south1
Primary Role: mds
Backup Server: south2
.
.
.
Power: on
.
.
.
Zobrazit stránku 136
1 2 ... 132 133 134 135 136 137 138 139 140 141 142 ... 361 362

Komentáře k této Příručce

Žádné komentáře